Confined Space Entry Permit Checklist
A pre-entry reference for permit-required confined spaces under OSHA 1910.146. Not a substitute for your workplace’s actual written entry permit or formal training — use this alongside both.
Before Testing
- Confirm the monitor is calibrated and bump-tested for the day
- Confirm entrant, attendant, and entry supervisor roles are assigned
- Confirm isolation measures are in place (lockout/tagout, blanking, disconnecting) as needed
Atmospheric Testing — In This Order
- Oxygen content: confirm within 19.5%–23.5%
- Flammable/combustible gas: confirm below 10% of the Lower Explosive Limit (LEL)
- Toxic gases (including H2S): confirm below the permissible exposure limit
- Test at multiple levels within the space, not just at the opening
The Written Permit Must Include
- Measures used to isolate the space and control hazards
- Acceptable entry conditions
- Atmospheric test results, including who tested and what equipment was used
- Name of the nearest rescue service and their expected response time
During Entry
- Continue atmospheric monitoring throughout the entry — conditions can change
- Maintain continuous communication between attendant and entrants
- Evacuate immediately if monitor alarms or conditions change unexpectedly
Rescue Readiness
- If rescue response time exceeds roughly 5–10 minutes for a space that could reach IDLH conditions, confirm on-site rescue capability is in place
- Confirm rescue equipment is staged and accessible before entry begins
Related certification: Hydrogen Sulfide (H2S) Certification
Related guides
- Why You Can’t Trust Your Nose Around H2S
- H2S and Confined Spaces: Why They Go Together
- The Correct Order for Testing a Confined Space Atmosphere
- H2S Alarm Levels: What 20 ppm vs. 100 ppm Actually Means
This checklist is a quick reference and does not replace your workplace’s written entry permit program or formal OSHA training. © Shield Certificates — shieldcerts.com